Product Specifications
A
- This section provides the environmental, physical, and electrical specifications for the SPARCcluster 1000 and SPARCcluster 2000 High Availability Servers. The contents of this Appendix are as follows:
-
-
Caution - Make no mechanical or electrical modifications to the cabinets. Sun is not responsible for the regulatory compliance if a cabinet is modified.
A.1 Physical Specifications
- Physical specifications are presented in the tables which follow.
A.1.1 SPARCcluster 1000HA Server
-
Caution - Make no mechanical or electrical modifications to the cabinets. Sun is not responsible for the regulatory compliance if a cabinet is modified.
-
Table A-1
| U.S. | Metric | Comments |
| Height | 56 in | 143 cm |
|
| Width | 30 in | 77 cm |
|
| Depth | 39 in | 99 cm |
|
| Weight: Main cabinet | 650 lb | 300 kg |
Approximate weight -- depending upon configuration
|
| Weight: Expansion cabinet | 1000 lb | 455 kg | Approximate weight -- depending upon configuration |
| Power cord | 15 ft | 4.6m |
-
Table A-2
| U.S. | Metric |
| Front | 36 in | 92 cm |
| Rear | 36 in | 92 cm |
| Left | 36 in | 92 cm |
| Right | 36 in | 92 cm |
A.1.2 SPARCcluster 2000 HA Server
-
Caution - Make no mechanical or electrical modifications to the cabinets. Sun is not responsible for the regulatory compliance if a cabinet is modified.
-
Table A-3
| U.S. | Metric | Comments |
| Height | 56 in | 143 cm |
|
| Width | 30 in | 77 cm |
|
| Depth | 39 in | 99 cm |
|
| Weight | 900 lb | 360 kg |  Approximate weight -- depending upon configuration
|
| Power cord | 15 ft | 4.6m |
-
Table A-4 SPARCcluster 2000 High Availability Server
- Clearance and Service Access
-
| U.S. | Metric |
| Front | 36 in | 92 cm |
| Rear | 36 in | 92 cm |
| Left | 36 in | 92 cm |
| Right | 36 in | 92 cm |
A.2 Electrical Specifications
A.2.1 SPARCcluster 1000HA Server
-
Table A-5 provides specifications for the system cabinet equipped with two SPARCserver 1000E systems and three SPARCstorage arrays.
-
Table A-5
| Parameter |
| Value |
| Input current | Voltage range | 200-240 VAC |
| Current, maximum | 17A at 220 VAC input |
| Current frequency range | 47-63 Hz |
| Input power rating | Total continuous power | 3480W |
| Volt-Ampere rating | 3740 VA |
| BTU rating | 11,850 BTU |
| Power factor | 0.91-0.96 |
| Plug type | U.S. | NEMA L6-30P for 200-240 VAC |
| International | 32A, single phase IEC 309, connected for 220-240 VAC |
-
Table A-6 provides specifications for an expansion cabinet equipped with five SPARCstorage arrays.
-
Table A-6 Electrical Specifications for the Expansion Cabinet
- Housing Five SPARCstorage arrays
-
| Parameter |
| Value |
| Input current | Voltage range | 200-240 VAC |
| Current, maximum | 24A at 220 VAC input |
| Current frequency range | 47-63 Hz |
| Input power rating | Total continuous power | 5016W |
| Volt-Ampere rating | 5280 VA |
| BTU rating | 17,104 BTU |
-
Table A-6 Electrical Specifications for the Expansion Cabinet
- Housing Five SPARCstorage arrays (Continued)
-
| Parameter |
| Value |
| Power factor |
| 0.91-0.96 |
| Plug type | U.S. | NEMA L6-30P for 200-240 VAC |
| International | 32A, single phase IEC 309, connected for 220-240 VAC |
A.2.2 SPARCcluster 2000HA Server
-
Table A-7 provides specifications for one (of the two) server cabinets equipped with two SPARCstorage arrays.
-
Table A-7
| Parameter |
| Value |
| Input current | Voltage range | 200-240 VAC |
| Current, maximum | 24.7A at 220VAC input |
| Current frequency range | 47-66 Hz |
| Input power rating | Total continuous power | 5100 W |
| Volt-Ampere rating | 5430 VA |
| BTU rating | 17,390 BTU |
| Power factor | 0.91-0.96 |
| Plug type | U.S. | NEMA L6-30P for 200-240 VAC |
| International | 32A, single phase IEC 309, connected for 220-240 VAC |
-
Note - The electrical specifications for the expansion cabinet are the same as that described in Table A-6 for the 1000HA server expansion cabinet.
A.3 Environmental Specifications
- The environmental specifications for both the SPARCcluster 1000HA and SPARCcluster 2000HA servers are the same. Avoid temperature extremes and keep the work area clean. Maintain the operating conditions shown below:
-
Table A-8
| Operating | Nonoperating |
| Specification | U.S. | Metric | U.S. | Metric |
| Temperature | 50. to 86.F | 10. to 30.C | -4. to 140.F | -20. to 60.C |
| Altitude | 10,000 ft | 3,048 m | 40,000 ft | 12,192 m |
| Humidity | 20% to 80% RH | 5% to 95% RH | 20% to 80% RH | 5% to 95% RH |
- Sun suggests installing the SPARCcluster HA servers in a computer room environment. Computer room installation provides security access to computers and stored information and affords control over environmental factors such as temperature, humidity, and airborne dust. Computer room installation also protects equipment from fire, flood, or other danger originating in the building.
|
|