Specifications
3
- This section provides the environmental, physical, and electrical specifications for the SPARCcluster 1000 High Availability and SPARCcluster 2000 High Availability Servers.
-
Caution - Make no mechanical or electrical modifications to the cabinets. Sun is not responsible for the regulatory compliance if a cabinet is modified.
3.1 Physical Specifications
- Physical specifications are presented in the tables which follow.
3.1.1 SPARCcluster 1000 High Availability
-
Caution - Make no mechanical or electrical modifications to the cabinets. Sun is not responsible for the regulatory compliance if a cabinet is modified.
-
Table 3-1
| U.S. | Metric | Comments |
| Height | 56 in | 143 cm |
|
| Width | 30 in | 77 cm |
|
| Depth | 39 in | 99 cm |
|
| Weight | 650 lb | 300 kg |
Approximate weight -- depending upon configuration
|
| Power cord | 15 ft | 4.6m |
-
Table 3-2
| U.S. | Metric |
| Front | 36 in | 92 cm |
| Rear | 36 in | 92 cm |
| Left | 36 in | 92 cm |
| Right | 36 in | 92 cm |
3.1.2 SPARCcluster 2000 High Availability
-
Caution - Make no mechanical or electrical modifications to the cabinets. Sun is not responsible for the regulatory compliance if a cabinet is modified.
-
Table 3-3
| U.S. | Metric | Comments |
| Height | 56 in | 143 cm |
|
| Width | 30 in | 77 cm |
|
| Depth | 39 in | 99 cm |
|
| Weight | 900 lb | 360 kg |  Approximate weight -- depending upon configuration
|
| Power cord | 15 ft | 4.6m |
-
Table 3-4
| U.S. | Metric |
| Front | 36 in | 92 cm |
| Rear | 36 in | 92 cm |
| Left | 36 in | 92 cm |
| Right | 36 in | 92 cm |
3.1.3 Expansion Cabinet
-
Caution - Make no mechanical or electrical modifications to the cabinets. Sun is not responsible for the regulatory compliance if a cabinet is modified.
-
Table 3-5
| U.S. | Metric | Comments |
| Height | 56 in | 143 cm |
|
| Width | 30 in | 77 cm |
|
| Depth | 39 in | 99 cm |
|
| Weight | 1000 lb | 455 kg |
Approximate weight -- depending upon configuration
|
| Power cord | 15 ft | 4.6m |
-
Table 3-6
| U.S. | Metric |
| Front | 36 in | 92 cm |
| Rear | 36 in | 92 cm |
| Left | 36 in | 92 cm |
| Right | 36 in | 92 cm |
3.2 Electrical Specifications
3.2.1 SPARCcluster 1000 High Availability Server
-
Table 3-7 provides specifications for the system cabinet equipped with two SPARCserver 1000E systems and three SPARCstorage arrays.
-
Table 3-7
| Parameter |
| Value |
| Input current | Voltage range | 200-240 VAC |
| Current, maximum | 17A at 220 VAC input |
| Current frequency range | 47-63 Hz |
| Input power rating | Total continuous power | 3480W |
| Volt-Ampere rating | 3740 VA |
| BTU rating | 11,850 BTU |
| Power factor | 0.91-0.96 |
| Plug type | U.S. | NEMA L6-30P for 200-240 VAC |
| International | 32A, single phase IEC 309, connected for 220-240 VAC |
3.2.2 SPARCcluster 2000 High Availability Server
-
Table 3-8 provides specifications for one server cabinet equipped with two SPARCstorage arrays.
-
Table 3-8
| Parameter |
| Value |
| Input current | Voltage range | 200-240 VAC |
| Current, maximum | 24.7A at 220VAC input |
| Current frequency range | 47-66 Hz |
| Input power rating | Total continuous power | 5100 W |
| Volt-Ampere rating | 5430 VA |
| BTU rating | 17,390 BTU |
-
Table 3-8
| Parameter |
| Value |
| Power factor |
| 0.91-0.96 |
| Plug type | U.S. | NEMA L6-30P for 200-240 VAC |
| International | 32A, single phase IEC 309, connected for 220-240 VAC |
-
Table 3-9
| Parameter |
| Value |
| Input current | Voltage range | 200-240 VAC |
| Current, maximum | 24A at 220 VAC input |
| Current frequency range | 47-63 Hz |
| Input power rating | Total continuous power | 5016W |
| Volt-Ampere rating | 5280 VA |
| BTU rating | 17,104 BTU |
| Power factor | 0.91-0.96 |
| Plug type | U.S. | NEMA L6-30P for 200-240 VAC |
| International | 32A, single phase IEC 309, connected for 220-240 VAC |
3.3 Environmental Specifications
- The environmental specifications presented in Table 3-10 apply to the SPARCcluster 1000- and SPARCcluster 2000 High Availability servers. Avoid temperature extremes and keep the work area clean. Maintain the operating conditions shown in Table 3-10.
-
Table 3-10
| Operating | Nonoperating |
| Specification | U.S. | Metric | U.S. | Metric |
| Temperature | 50. to 86.F | 10. to 30.C | -4. to 140.F | -20. to 60.C |
| Altitude | 10,000 ft | 3,048m | 40,000 ft | 12,192m |
| Humidity | 20% to 80% RH | 5% to 95% RH | 20% to 80% RH | 5% to 95% RH |
- Sun suggests installing the SPARCcluster High Availability Server in a computer room environment. A computer room installation makes it possible to ensure secure access to computers and stored information. In addition, it can fulfill the requirements for a controlled environment, especially with regard to temperature, humidity, and airborne dust. A computer room installation usually provides improved protection against damage by fire, flood, or other danger originating in the building.
|
|