SPARCcluster HA Server Hardware Planning and Installation
この本のみを検索
PDF 文書ファイルをダウンロードする

Specifications

3

This section provides the environmental, physical, and electrical specifications for the SPARCcluster 1000 High Availability and SPARCcluster 2000 High Availability Servers.

CAUTION Caution - Make no mechanical or electrical modifications to the cabinets. Sun is not responsible for the regulatory compliance if a cabinet is modified.

3.1 Physical Specifications

Physical specifications are presented in the tables which follow.

3.1.1 SPARCcluster 1000 High Availability


CAUTION Caution - Make no mechanical or electrical modifications to the cabinets. Sun is not responsible for the regulatory compliance if a cabinet is modified.

Table 3-1

U.S.MetricComments
Height56 in143 cm
Width30 in77 cm
Depth39 in99 cm
Weight650 lb300 kgグラフィック

Approximate weight -- depending upon configuration

Power cord15 ft4.6m
Table 3-2

U.S.Metric
Front36 in92 cm
Rear36 in92 cm
Left36 in92 cm
Right36 in92 cm

3.1.2 SPARCcluster 2000 High Availability


CAUTION Caution - Make no mechanical or electrical modifications to the cabinets. Sun is not responsible for the regulatory compliance if a cabinet is modified.

Table 3-3

U.S.MetricComments
Height56 in143 cm
Width30 in77 cm
Depth39 in99 cm
Weight900 lb360 kgImported image(187x208)

Approximate weight -- depending upon configuration

Power cord15 ft4.6m
Table 3-4

U.S.Metric
Front36 in92 cm
Rear36 in92 cm
Left36 in92 cm
Right36 in92 cm

3.1.3 Expansion Cabinet


CAUTION Caution - Make no mechanical or electrical modifications to the cabinets. Sun is not responsible for the regulatory compliance if a cabinet is modified.

Table 3-5

U.S.MetricComments
Height56 in143 cm
Width30 in77 cm
Depth39 in99 cm
Weight1000 lb455 kgグラフィック

Approximate weight -- depending upon configuration

Power cord15 ft4.6m
Table 3-6

U.S.Metric
Front36 in92 cm
Rear36 in92 cm
Left36 in92 cm
Right36 in92 cm

3.2 Electrical Specifications

3.2.1 SPARCcluster 1000 High Availability Server

Table 3-7 provides specifications for the system cabinet equipped with two SPARCserver 1000E systems and three SPARCstorage arrays.
Table 3-7
Parameter
Value
Input currentVoltage range200-240 VAC
Current, maximum17A at 220 VAC input
Current frequency range47-63 Hz
Input power ratingTotal continuous power3480W
Volt-Ampere rating3740 VA
BTU rating11,850 BTU
Power factor0.91-0.96
Plug typeU.S.NEMA L6-30P for 200-240 VAC
International32A, single phase IEC 309, connected for 220-240 VAC

3.2.2 SPARCcluster 2000 High Availability Server

Table 3-8 provides specifications for one server cabinet equipped with two SPARCstorage arrays.
Table 3-8
Parameter
Value
Input currentVoltage range200-240 VAC
Current, maximum24.7A at 220VAC input
Current frequency range47-66 Hz
Input power ratingTotal continuous power5100 W
Volt-Ampere rating5430 VA
BTU rating17,390 BTU
Table 3-8
Parameter
Value
Power factor
0.91-0.96
Plug typeU.S.NEMA L6-30P for 200-240 VAC
International32A, single phase IEC 309, connected for 220-240 VAC

Table 3-9
Parameter
Value
Input currentVoltage range200-240 VAC
Current, maximum24A at 220 VAC input
Current frequency range47-63 Hz
Input power ratingTotal continuous power5016W
Volt-Ampere rating5280 VA
BTU rating17,104 BTU
Power factor0.91-0.96
Plug typeU.S.NEMA L6-30P for 200-240 VAC
International32A, single phase IEC 309, connected for 220-240 VAC

3.3 Environmental Specifications

The environmental specifications presented in Table 3-10 apply to the SPARCcluster 1000- and SPARCcluster 2000 High Availability servers. Avoid temperature extremes and keep the work area clean. Maintain the operating conditions shown in Table 3-10.
Table 3-10

Operating Nonoperating
SpecificationU.S.MetricU.S.Metric
Temperature50. to 86.F10. to 30.C-4. to 140.F-20. to 60.C
Altitude10,000 ft3,048m40,000 ft12,192m
Humidity20% to 80% RH5% to 95% RH20% to 80% RH5% to 95% RH
Sun suggests installing the SPARCcluster High Availability Server in a computer room environment. A computer room installation makes it possible to ensure secure access to computers and stored information. In addition, it can fulfill the requirements for a controlled environment, especially with regard to temperature, humidity, and airborne dust. A computer room installation usually provides improved protection against damage by fire, flood, or other danger originating in the building.